INVERTER/CHARGER
PowerControl & PowerAssist: Yes
Transfer Switch: 32A
Maximum AC Input Current: 32A
Auxiliary Output: Yes (32A)
INVERTER
Input Voltage Range: 38 – 66V
Output Voltage: 230 VAC ± 2%
Frequency: 50 Hz ± 0,1% (1)
Cont. output power at 25°C (3): 3000VA / 2400W
Cont. output power at 40°C / 65°C: 2200W / 1700W
Maximum Apparent Feed-In Power: 2500VA
Peak Power: 5500W
Maximum Efficiency: 95%
Zero Load Power: 11W
Zero Load Power in AES Mode: 7W
Zero Load Power in Search Mode: 2W
CHARGER
AC Input Voltage Range: 187-265VAC
AC Input Frequency: 45 – 65 Hz
Charge Voltage 'Absorption': 57,6V
Charge Voltage 'Float': 55,2V
Storage Mode: 52,8V
Maximum Battery Charge Current (4): 35A
Battery Temperature Sensor: Yes
Programmable Relay (5): Yes
Protection (2): a - g
VE.Bus Communication Port: For parallel and three phase operation, remote monitoring and system integration
General Purpose Com. Port: Yes, 2x
SOLAR CHARGE CONTROLLER
Model: SmartSolar MPPT 250/70-Tr
Maximum Output Current: 70A
Maximum PV Power: 4000W
Maximum PV Open Circuit Voltage: 250V
Maximum Efficiency: 98%
Self-Consumption: 20mA
Charge Voltage 'Absorption', Default: 57,6V
Charge Voltage 'Float', Default Setting: 55,2V
Protection (2): a – e
GENERAL
Interfaces: VE.Can, USB, Ethernet, VE.Direct, wifi
Remote On-Off: Yes
Operating Temp. Range: -40 to +65°C (fan assisted cooling)
Humidity (Non-Condensing): max 95%
ENCLOSURE
Material & Colour: aluminium (blue RAL 5012)
Protection Category: IP21
Battery-Connection: M8 bolts
PV Connection: M6 bolts
230V AC-Connection: Screw terminals 13 mm2 (6 AWG)
Weight: 26kg
Dimensions: (hxwxd) 506 x 275 x 237mm
STANDARDS
Safety: EN-IEC 60335-1, EN-IEC 60335-2-29 EN-IEC 62109-1, EN-IEC 62109-2
Emission / Immunity: EN 55014-1, EN 55014-2 EN-IEC 61000-3-2, EN-IEC 61000-3-3 IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
(1) Can be adjusted to 60 Hz
(2) Protection key: a) output short circuit b) overload c) battery voltage too high d) battery voltage too low e) temperature too high f) 230 VAC on inverter output g) input voltage ripple too high
(3) Non-linear load, crest factor 3:1
(4) At 25°C ambient
(5) Programmable relay which can be set for general alarm, DC under voltage or genset start/stop function. AC rating: 230